The EH5200 series is a new type high-frequency online UPS. Adopts advanced DSP digital control technology to effectively improve product performance and system reliability, and higher power density small size, light weight and high work efficiency. Effectively solve power problems such as power cut-off, Grid over voltage/low voltage, voltage instantaneous drop, amplitude reduction, high voltage pulse, surge voltage, harmonic distortion, clutter interference, frequency fluctuation and provide best power for load.
Model | H1K | H1KS | H2K | H2KS | H3K | H3KS |
---|---|---|---|---|---|---|
Capacity | ||||||
VA/W | 1KVA/0.9KW | 2KVA/1.8KW | 3KVA/2.7KW | |||
Input | ||||||
Voltage Range | Full Load:160±50%VAC~300±50%VAC;Half Load:110±50%VAC~300±50%VAC | |||||
Frequency Range | 40-70Hz | |||||
Phase | Single phase two wire+ground wire | |||||
Distortion | <5% | |||||
Power factor | 0.99 | |||||
Generator input | support | |||||
Output | ||||||
Voltage | 220 (1±1%)VAC | |||||
Frequency (same frequency mode) | 47~53Hz/57~63Hz | |||||
Power Factor | 0.9 | |||||
Frequency (battery mode) | 50±0.25Hz or 60±0.25Hz | |||||
Crest ratio | 03:01 | |||||
Harmonic distortion | ≤3%THD (Linear load) | |||||
≤6%THD (Nonlinear load) | ||||||
Output waveform | Pure Sine Wave | |||||
Socket | Universal socket *2 | Universal socket *4 | Universal socket *3+Terminal block | |||
Over Load | 100%-110%: warning sound; 110%-130%:Automatically turns off after 1 minute, or switch to bypass mode when input correct; >130%:Turn off immediately, or switch to bypass mode when the input correct | |||||
Efficiency | ||||||
Charging Mode | 85% | 88% | ||||
Battery Mode | 83% | 85% | ||||
Battery | ||||||
Battery Type | 12V/7AH | / | 12V/7AH | / | 12V/7AH | / |
Battery Number | 3 | 6 | 8 | |||
Equipment time (full load) | >5mins | >5mins | >5mins | |||
Charging Time(90%) | 8h | 8h | 8h | |||
Charge battery (max) | 1.0A | 4.0 | 1.0A | 4.0 | 1.0A | 4.0 |
Rated charging voltage | 41.0±1%VDC | 82.1±1%VDC | 109.4±1%VDC | |||
Temperature detection | support | |||||
Conversion time | ||||||
Utility to Battery | 0ms | |||||
Inverter to bypass | 4ms | |||||
Utility Priority Mode | support | |||||
Warning Alarm | ||||||
Battery Mode | alarm every 4 seconds | |||||
Low Power | alarm every one second | |||||
Over Load | alarm 2 every second | |||||
Fault | continuous alarm | |||||
Shape | ||||||
Dimension (D*W*H) mm | 350*145*220 | 425*190*320 | ||||
Net weight(Kg) | 12 | 7 | 24 | 11 | 29 | 12 |
Connector | ||||||
Micro RS-232 | Windows,Linux,Sun Solaris,IBM Aix,Compaq True64,SGIRIX,FreeBSD,HP-UX and MAC | |||||
USB(Optional) | Windows & MAC | |||||
Rabbet(Optional) | SNMP/AS400 Relay Card/Rs485 | |||||
EPO(Optional) | Support emergency shutdown |